« October 2006 | Main | July 2006 »
Friday, September 22, 2006
EtherNet/IP Seminar in Chicago
On September 21, 2006, the ODVA held a free EtherNet/IP seminar in the Rosemont suburb of Chicago, IL. Four engineers from Contemporary Controls attended, including Joe Stasiek pictured below.
Most Industrial Ethernet networks are modified for a specific application and they differ in language, data handling and Ethernet devices. EtherNet/IP™ (promoted by ODVA) fully complies with Ethernet and Internet standards and uses the media-independent industrial protocol, Common Industrial Protocol — or CIP™.
Seminar subjects included overviews of Industrial Ethernet, CIP and EtherNet/IP and a roadmap for EtherNet/IP development in the areas of safety and motion.
Powering Industrial Ethernet
How does the voltage sourcing for your Industrial Ethernet compare with that of others? A recent survey asked "What's the most common low-voltage power source used in your Ethernet applications?" By far the most common supply voltage is 24 VDC. The responses were:
24 VDC: 45%
24 VAC: 20%
12 VDC: 17%
12 VAC: 20%
Other: 10%
Wednesday, September 06, 2006
An RSTP No-No
A while ago a customer complained of a very long recovery time (from one to four minutes) for his RSTP network. He had connected two managed switches (which had no fiber ports) through four unmanaged switches (RSTP-unaware) which he was using as media converters to provide a fiber backbone. The illustration below shows the six-switch network with the pertinent switch ports numbered. The RSTP protocol had forced the blue link inactive, making it the backup link. Then, to test his RSTP performance, the customer interrupted the red link — causing the blue backup link to activate. The fiber backbone is indicated by the green links. Analysis revealed that the unmanaged switch address tables were the source of the problem.
The RSTP protocol had elected MS 1 as the root device, placing its ports 2 and 6 in the forwarding state. On MS 2, port 6 was placed in the discarding state to stop messages from looping through the blue link.
Broadcasts affect the address tables of all switches. This is true even if a switch is not serving any message path — as is the case with UMS 3 and UMS 4 while the blue backup link is inactive. Consequently, UMS 3 and UMS 4 correctly register both PC 1 and PC 2 as connected on port 3 of each switch.
When the network topology is reconfigured due to an interruption of the red link, UMS 3 and UMS 4 become part of the communication path, but they will be ignorant of the reconfiguration. Consequently, UMS 3 and UMS 4 will still try to forward all messages to the left via port 3 of each switch — although the reconfiguration requires that messages from PC 1 to PC 2 exit UMS 3 and UMS 4 to the right via ports 4 of each switch. This means that once the blue backup link becomes active, messages destined for PC 2 will be lost until the address tables of UMS 3 and UMS 4 are corrected.
Switches filter, forward or flood received messages. They flood messages when the destination MAC address is not in their address table. They forward messages when the destination MAC address is in their address table. They filter messages (throw them away) when the destination MAC address is associated with the same port on which the messages arrive.
Message filtering was causing the problem for the customer. The solution was to use media converters (having no address tables) that pass link status between the managed switches.
It is unwise for your RSTP network to have a mix of switches that are RSTP-aware with those which are RSTP-unaware. As can be seen in this example, sometimes the effects of such mixing can impair network performance.