Headquartered in Buffalo Grove, Illinois, Siemens Building Technologies is a leading supplier of products, services and solutions for fire alarm and life safety protection, as well as building automation and security.
Recently, Siemens began a project to offer their customers stronger integration between the company's building automation and fire safety systems. Siemens planned to enhance the versatile APOGEE Insight building automation software to allow facility operators to monitor and control their automation and life safety systems from a single workstation platform, as well as share information between those building systems.
"There's an advantage to having this capability," says Tom Rule, Product Manager for Siemens. "Using an integrated system, facility managers can gain a clear picture of the status of each subsystem within the facility. This allows them to provide a greater environment of safety, and enhance the productivity of their workforce by using Insight Life Safety workstations that carry UL Listings for fire, security, and critical process management applications. In addition, we are able to retrieve diagnostic information from reports and to configure the system to automatically initiate control sequences between building systems."
With the new system, the Alarm Bar application would enable an operator to view the current status of the fire, security, and building automation systems. From the Alarm Bar, operators with proper permissions would have the ability to acknowledge events and issue commands to the system.

Siemens chose Ethernet to provide the systems's communications. A portion of the project required UL 864 Recognition on workstation components for use in fireprotective signaling systems. All components, including workstations, monitors, and Ethernet switches used for communications between workstations, had to pass stringent hardware tests in order to acquire a UL Listing on the system. UL 864 Recognition on the Ethernet switches is required to meet the NFPA 72 code requirements that any communications path used for transmitting critical life safety data be listed for fire-protective signaling use. In the fire alarm industry that communication path is known as the Signaling Line Circuit.
"Only if every component from the smoke detector to the workstation used for monitoring the system, including Ethernet switches, is UL Recognized for fireprotective signaling use, can the entire system be considered UL Listed," explains Rule. "If any component on the signaling line circuit is not Recognized, then the Listing for the entire system is lost."
For isolation purposes, every networked Insight workstation that is listed for fire-protective signaling use must be connected to the Ethernet network through one of these special switches. Switches were employed because they can extend network distance beyond a single collision domain compared to repeating hubs while increasing performance. Performance is critical to ensure that emergency messages are delivered as quickly as possible.
In order to allow Ethernet switches to be powered from the fire alarm panel, with its inherent battery backup power, Siemens chose Contemporary Controls' EIS Ethernet Interconnect Switch Series, which is a UL 864 Recognized Component. The UL recognized component mark is rarely seen by the customer, but is often part of a larger end-product that is UL Listed by the fire alarm system supplier. For an end-product to be UL Listed, the product is tested by UL to determine if it meets the requirements established by UL's published Standards of Safety. A UL recognized component has already been evaluated and tested in accordance with UL's component safety standards, streamlining the qualification process for the end-product.
By having the fire alarm system supplier specifying a Contemporary Controls' EIS Ethernet switch to be used within the system, the supplier is not required to perform additional testing on this component. Several fire alarm and security firms have already specified the EIS series as part of their system thereby improving their time-to-market.
Components that bear the UL Recognized Component mark are separately covered under UL's Follow-Up Surveillance program to ensure continued compliance and prevent unpleasant surprises when an end-product is inspected.
"Contemporary Controls was willing to secure and maintain UL 864 Recognition on the Ethernet switches," said Rule. "They had equipment configurations to meet our needs and they were able to provide local technical support."
Both the EIS eight-port copper Ethernet 
          switch and the EIS six-port copper/fiber optic unit met the following high-voltage testing levels:
        The 
        units can survive  a temperature of 50°C 
        and 95° humidity for 24 hours and can operate 
        on a backup power source of 24 VDC supplied by the fire alarm panel.
        
        The EIS8-100T provides eight 0/100 Mbps copper ports utilizing RJ-45 connectors. 
        The EIS6-100T/FT is a similar design but with only four copper ports and 
        two fiber optic ports utilizing ST connectors. The fiber optic units can 
        be deployed over long distances (up to 2 km) and in locations where high 
        noise immunity is desired. The switches offer wide range AC/DC operation. 
        But for this application, the switches only need to operate from low voltage 
        DC power. The units are mounted in a special enclosure that is also UL 
        Recognized for fire-protective signaling use. An MTBF of more than 40 
        years enable these units to be used with confidence. 
 Using the APOGEE system, workstations communicating 
          over Ethernet can be positioned side-by-side or could be miles apart. 
          Additionally, a combination of Fire workstations, which are Listed for 
          protective-signaling use, and non-Fire workstations that are not, can 
          reside on the same network. The fire alarm system can only 
          be controlled from Fire workstations, but data can be monitored from 
          both Fire and non-Fire workstations. 
          
          Fire, security and automation systems can be managed from APOGEE Insight 
          workstations. The APOGEE system enables data from all connected systems 
          available to all workstations on the network. For greater efficiency, 
          a database server centrally administrates the networked system over 
          a Management Level Network (MLN) that sends information where it needs 
        to go without encumbering every workstation with unnecessary data.

Rule says users are assigned access privileges that dictate what they 
          can and can't observe. "This permits the flexibility for centralized 
          monitoring and/or widespread distribution of information."
          
          UL Listed Fire workstations are typically located within the facility 
          or campus where the fire alarm system is installed; however, customers 
          often want the ability to monitor their systems remotely over the Internet 
          as well. APOGEE is flexible enough to provide this capability too.
          
          Insight Life Safety workstations can be a part of a dedicated network 
          of Insight workstations or they can be part of a customer's enterprise 
          (or corporate) network. When connected to a corporate network, the Insight 
          workstations must reside on a dedicated IP subnet/ broadcast domain 
          isolated from the corporate network. Rule says this is accomplished 
          by using a router which prevents traffic from the corporate network 
          (i.e. broadcasts and other non-Insight messages) from interfering with 
          the ability for fire alarm signals to pass between Fire workstations. 
          He explains that this ensures all of the bandwidth on the dedicated 
          network is available for Insight communications. This configuration 
          increases data throughput and eliminates security issues that could 
          arise. 
          
          The system architecture locks together through the switches. Typically, 
          one switch is located at each Insight Fire Workstation on a Management 
          Level Network. A multiple of EIS8-100T's, connected by Category 5 cabling, 
          are employed when these workstations are short distances apart          on the network-under 300 m. Segment lengths cannot exceed 100 m requiring 
          the use of multiple switches. The EIS6-100T/FT, for distances up to 
          2 km, provides interference-free fiber medium for connecting these workstations. 
          
          
          Typically one workstation is installed at the security desk so the operator 
          may take appropriate action to any life safety, security, or automation 
          related events. Copper or fiber connection to the next workstation is 
          determined by distance. The APOGEE workstations all reside on the Ethernet 
          network and serve the purpose of monitoring operation and annunciating 
          critical information. Ultimately, they are tied into the fire panels 
          via a Siemens proprietary network. In some facilities, 20 or more workstations 
          might be installed. 
          
          Rule says one workstation is often positioned for facilities maintenance 
          department use in order to ensure that maintenance has first hand knowledge 
          of any activations or faults on the fire alarm system. By having fire 
          alarm information available within their building automation management 
          system, the maintenance staff can immediately determine the precise 
          location of any problem and make adjustments as necessary. This eliminates 
          the need for security to communicate the need for action on
          the fire alarm system to the facilities maintenance staff and expedites 
          the return to normal operation.

Additional workstations might also be installed at a facilities director's office or at critical points within the facility that are most effected by operation of various building systems. By having access to information from all building systems within a network of building management workstations, people associated with a facility can get access to the information they need, when and where they need it, to ensure the optimal performance of the facility.
Reliability was vital in this project because it is a life safety system. Siemens had to be assured that the life safety system would continue to function as intended, to save lives and minimize damage to the facility.
"By working with Contemporary Controls, we felt 
          confident that our life safety system would not fail us," says 
          Rule. "We 
          count on Contemporary Controls to provide reliable products and to have 
          parts and expertise available at all times."