BAScontrol22S 22-point BACnet/IP Client Sedona Unitary Controller

Product Overview

The BAScontrol22S is a 22-point unitary controller which supports BACnet client/server operation over BACnet/IP or BACnet MS/TP. The controller complies with the B-ASC device profile having a convenient mix of 8 universal inputs, 4 binary inputs, 4 analog outputs, and 6 binary outputs. Unique to the unit are 48 web components which link Sedona wiresheet readable/writeable data to webpages, and 24 virtual points which link Sedona wiresheet readable/writeable data to a BACnet client.

The device is fully webpage configurable and freely programmable using Sedona's function block programming methodology of assembling components onto a wiresheet to create applications. The unit can be programmed using the BAScontrol Toolset. The controller is powered by a 24VAC/VDC source. Rugged design, low profile, and wide temperature operation make it suitable for indoor or outdoor use.

Versatile Control Device — Unitary controller or remote Ethernet I/O

  • BACnet/IP and BACnet MS/TP client/server
  • BACnet B-ASC device profile
  • License-free Sedona function block programming
  • Programmable via BAScontrol Toolset
  • Configurable with a common web browser
  • 10/100 Mbps auto-negotiation Ethernet port
  • NTP or manually settable real-time clock
  • COV subscriptions — 14 binary and 2 analog
  • Wide operating temperature range of -40°C to +75°C

Flexible Input/Output — 22-points of physical I/O

  • Eight configurable universal inputs: thermistor, resistance, voltage, binary, pulse
  • Four voltage-free binary inputs
  • Four analog outputs
  • Six relay outputs

Product Details

The BAScontrol22S utilizes a 32-bit ARM7 processor with 512 kB of flash memory, plus a 16 Mbit serial flash file system for storing configuration data and an application program. By operating at the BACnet/IP level, the BAScontrol22S can share the same Ethernet network with supervisory controllers, operator workstations or IP routers. A 10/100 Mbps auto-negotiating Ethernet port supports protocols such as BACnet/IP, Sedona Sox, HTTP, and FTP. The unit can be configured for a fixed IP address or can operate as a DHCP client receiving its IP address from a DHCP server. An LED indicator identifies a link condition while flashing during data transfer. Depressing a hidden IP Reset switch returns the controller to default IP address settings.

In addition to the BACnet/IP Ethernet port, the BAScontrol22S has one non-isolated (2-wire) BACnet MS/TP serial port that can operate from 9.6-115.2 kbps. Transmit and receive LEDs flash on MS/TP traffic. A three-position DIP header block can invoke bias and termination for end-of-line (EOL) installations.

As a BACnet server device, the BAScontrol22S will respond to a BACnet client request by default over either the IP port or MS/TP port. This means that the BAScontrol22S can function as remote I/O to BACnet clients over IP or MS/TP without needing a Sedona program. Through webpage configuration of connected BACnet servers, the BAScontrol22S can function as a BACnet client to these devices over IP or MS/TP. This requires the use of Sedona network variables (NetVs) found in the NetV kit. This capability allows the BAScontrol22S to initiate messages over IP to other BACnet devices without the need for BACnet headend intervention.

Ordering Information

Model Description    
BASC-22SR BAScontrol22 Ethernet MS/TP $395

Accessories

Model Description                  
AI-XFMR Wall mount plug in transformer 120VAC input/24VAC output (details...) $39
AI-XFMR-E Wall mount plug in transformer 230VAC input/24VAC output (details...) $55
MDR-20-24 24VDC 20W DIN RAIL POWER SUPPLY (details...) $40
MDR-40-24 24VDC 40W DIN RAIL POWER SUPPLY (details...) $50
SDR-75-24 24VDC 75W DIN RAIL POWER SUPPLY (details...) $90
BAS-485-TER Active EIA-485 terminator (package 5 pieces) (detalis...) $285